More than just a compact air handling unit
Systemair CompactLine units are designed as a compact air handling units, manufactured according to the Ecodesign Directive, Machinery Directive, Low Voltage Directive, EMC Directive and other directives covering functional elements. Essential requirements, stated in the standards EN 1886, EN 13053 and EN 16798-3, have been accounted.
5 sizes available
Airflow up to 8,000 m³/h
Indoor and outdoor configurations
Vertical or horizontal duct connections
Plate or rotary heat exchanger
Access control solution
Eurovent-certified
The CompactLine casing consists of a mounting frame, panels and a base frame. with fully integrated controls.
The units are available in indoor and outdoor execution with additional protection against outdoor atmospheric conditions.
Compact and robust design with vertical or horizontal duct connections.
Calculated and measured performance certified by Eurovent.
The units are always produced according to the Ecodesign Directive, Machinery Directive, Low Voltage Directive, EMC Directive and other directives covering functional elements.
Essential requirements, stated in the standards EN 1886, EN 13053 and EN 16798-3, have been accounted for.
Mechanical properties in accordance with EN 1886:
Thermal transmittance class T2
Thermal bridging class TB2 / TB3
Mechanical strength casing class D1
Casing air leakage class L1 / L2
)
Doors with hinges and removable panels are available to access the interior of the air handling unit.
The galvanized steel base frame protects the lower section of the air handling unit against corrosion and damage, ensures structural strength and rigidity, and enables the unit transport and assembly on the building. The following base frame versions are possible:
One-piece unit
125 mm base frame (no feet),
125 mm base frame + 110~175 mm adjustable feet.
Devided unit
Without base frame, only with 110~175 mm adjustable feet.
The base frame comes with lifting brackets for easier lifting and installation.
Strong and robust hinges and handles increase the lifetime of your unit casing, increase security with regard to the unit’s moving parts and increase casing airtightness.
Double-shell insulated panels come with an interrupted thermal bridge. The panels are bolted onto the frame from the outside.
Insulation:
Material type: rockwool
Insulation thickness: 50 mm
Insulation density: 100 kg/m3
Non-combustible, class A1 according to EN 13501-1
Possible materials for internal panel jacket, external panel jacket and internal built-in elements:
ZnAlMg coated steel
The aluminum profile frame (AlMgSi) is made of hollowed aluminum sections (EN AW-6060) and rounded nylon corners (PA6+GF20%).
Possible versions of aluminum sections:
with an interrupted thermal bridge,
painted aluminum RAL9006.
Self-adhesive sealing tape is used for joints between the fixed non-removable panels and the frame.
Self-adhesive or foamed sealing tape on doors, depending on standard or hygienic execution.
All sealing tapes and the poured PU sealing compound have a closed-cell structure and are resistant to molds and other microorganisms.
Depending on the purpose of use and the requirements of the client, the following sealing options are available:
sealant is applied to the bottom openings
of internal casing (standard)
sealant is applied to all fixed panel
openings of external casing (outdoor)
)
Units can be selected with airCalc++ selection tool, which is frequently updated and allows optimization of every option.